Box Fill Calculator — NEC 314.16 Cubic Inches
Who this is for: For electricians roughing-in residential boxes — especially remodels where a deeper box is cheaper than a failed inspection — and inspectors double-checking a crowded multi-gang.
Enter the box volume and everything that lands in it — wires, clamps, devices, grounds — and see the 314.16 cubic-inch tally with pass/fail.
Quick answer: Box fill = every item's cubic-inch charge from NEC 314.16(B) summed against the box's marked volume. 14 AWG charges 2.00 in³ per conductor, clamps one charge per box, devices two conductors' worth each, grounds one charge total. A 14 in³ box holding three 14 AWG wires, a clamp, a device and grounds totals exactly 14.0 in³ — full.
Marked on the box
2.00 in³ each
any # of clamps = 1 charge
all grounds = 1 charge
| Volume per conductor | 14 AWG 2.00 · 12 AWG 2.25 · 10 AWG 2.50 in³ |
|---|---|
| Clamps | 1 allowance per box (largest conductor) |
| Devices & fittings | 2 × largest conductor, each |
| Ground wires | 1 allowance total |
| Example | 14 in³ box: 3×14 AWG + clamp + device + grounds = 14.0 in³ ✓ |
| Status | Figures follow NEC 2017+ reference tables (310.16 ampacity, Chapter 9 conduit fill, 314.16 box fill, 240.4(D) small-conductor caps) and standard equal-friction duct sizing, compiled September 2026. Estimates only — final designs belong to a licensed electrician / HVAC designer per local code. |
What counts in a box fill calculation?
NEC 314.16 assigns every item in the box a cubic-inch charge: each conductor by size (14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³), one clamp allowance per box regardless of clamp count (charged at the largest conductor present), each support fitting or device at twice the largest conductor's volume, and all equipment grounding conductors together as a single allowance. Add the charges up and they must fit the box's marked cubic-inch volume. Example: a 14 in³ box with three 14 AWG conductors, one clamp, one device and grounds totals 14.0 in³ — exactly full, so pass — and a fourth conductor tips it over.
Common uses
- Checking whether a ceiling box can take one more cable before drywall
- Sizing a multi-gang box for dimmers with pigtails everywhere
- Explaining to a builder why the box went from 1-gang metal to a 22.5 in³ cube
- Verifying a junction box buried behind insulation meets 314.16 and 314.29 access rules