Wire Size Calculator — Ampacity with NEC 240.4(D) Caps
Who this is for: For electricians laying out branch circuits who want the Table 310.16 answer with the 240.4(D) small-conductor limits baked in — no flipping between tables mid-job.
Enter load current and terminal temperature rating — get the minimum AWG by ampacity, with the 240.4(D) small-conductor caps already applied.
Quick answer: Wire size by ampacity: pick the smallest Table 310.16 conductor that meets your load at the terminal temperature rating, then apply the 240.4(D) caps — 14 AWG max 15 A, 12 AWG max 20 A, 10 AWG max 30 A. A 50 A load at 75°C lands on 8 AWG copper (table value exactly 50 A).
Amps the circuit carries at steady state.
| Size | Table @ 75°C | 240.4(D) cap | Effective |
|---|---|---|---|
| 14 AWG | 20 A | 15 A | 15 A |
| 12 AWG | 25 A | 20 A | 20 A |
| 10 AWG | 35 A | 30 A | 30 A |
| Ampacity table | NEC Table 310.16 (60/75/90°C) |
|---|---|
| 240.4(D) caps | 14 AWG → 15 A · 12 AWG → 20 A · 10 AWG → 30 A |
| Working column | 75°C for most terminations |
| Example | 50 A @ 75°C → 8 AWG copper |
| Not included | Voltage drop, ambient/bundle derating — check separately |
| Status | Figures follow NEC 2017+ reference tables (310.16 ampacity, Chapter 9 conduit fill, 314.16 box fill, 240.4(D) small-conductor caps) and standard equal-friction duct sizing, compiled September 2026. Estimates only — final designs belong to a licensed electrician / HVAC designer per local code. |
How does this wire size calculator pick a size?
It reads NEC Table 310.16 at the insulation temperature you choose — 60°C (older NM terms), 75°C (most modern terminations) or 90°C (heat-rated cable, but terminations usually still govern at 75°C) — and finds the smallest conductor whose allowable ampacity meets your load. Then it applies 240.4(D), the small-conductor rule that caps 14 AWG at 15 A, 12 AWG at 20 A and 10 AWG at 30 A regardless of the table figure. The result shows both the table value and the effective cap, so you can see when 240.4(D) is the binding constraint. Note this is the ampacity pick only — long runs also need the voltage-drop check above, and derating for ambient temperature or bundled conductors stacks on top.
Common uses
- Picking branch-circuit conductors for a named breaker size
- Sanity-checking a plan marked with generous but oversized copper
- Explaining to an apprentice why 12 AWG can't feed a 25 A breaker even though the table says 25 A
- Comparing 60°C vs 75°C terminals on replacement equipment