Wire Ampacity Chart (NEC Table 310.16) — Copper, 60/75/90°C
One table sits under every wire-size decision in American branch-circuit work: NEC Table 310.16. This page prints the copper columns with the small-conductor caps applied, plus the circular-mil areas that voltage-drop math needs.
Quick answer: NEC Table 310.16 copper: 14 AWG = 15/20/25 A (60/75/90°C), 12 AWG = 20/25/30, 10 AWG = 30/35/40, 8 AWG = 40/50/55, 6 AWG = 55/65/75, 4 AWG = 70/85/95, 2 AWG = 95/115/130, 1/0 = 125/150/165, 4/0 = 195/230/260. But 240.4(D) caps small conductors: 14→15 A, 12→20 A, 10→30 A for everyday circuits.
The table (copper, dry locations)
- 14 AWG — 15 / 20 / 25 A — cap 15 A — 4,110 cmil
- 12 AWG — 20 / 25 / 30 A — cap 20 A — 6,530 cmil
- 10 AWG — 30 / 35 / 40 A — cap 30 A — 10,380 cmil
- 8 AWG — 40 / 50 / 55 A — 16,510 cmil
- 6 AWG — 55 / 65 / 75 A — 26,240 cmil
- 4 AWG — 70 / 85 / 95 A — 41,740 cmil
- 3 AWG — 85 / 100 / 115 A — 52,620 cmil
- 2 AWG — 95 / 115 / 130 A — 66,360 cmil
- 1 AWG — 110 / 130 / 145 A — 83,690 cmil
- 1/0 — 125 / 150 / 165 A — 105,600 cmil
- 2/0 — 145 / 175 / 195 A — 133,100 cmil
- 3/0 — 165 / 200 / 225 A — 167,800 cmil
- 4/0 — 195 / 230 / 260 A — 211,600 cmil
- 250 kcmil — 215 / 255 / 290 A — 250,000 cmil
Which column do I use?
The lowest rating in the chain: conductor insulation, termination rating, and device rating. Modern breakers and equipment terminations are typically 75°C, so the 75°C column is the working default. The 90°C column exists mostly as a derating starting point — you may start at 90°C values when applying ambient/bundle correction factors, but you must land at or below the 75°C termination value.
The 240.4(D) override
For branch circuits up to household sizes, the small-conductor rule caps protection regardless of the table: 14 AWG at 15 A, 12 AWG at 20 A, 10 AWG at 30 A. That's why 12 AWG 'rated 25 A' at 75°C still can't feed a 25 A breaker in a normal circuit. Exceptions exist (motor circuits, some 90°C-use cases with specific conditions), but the caps are the everyday rule.
What the table doesn't include
- Voltage drop — a 15 A, 200 ft circuit passes this table and fails the 3% target badly.
- Derating — ambient heat above 30°C and bundling (>3 CCC in a raceway) multiply downward.
- Aluminum — separate columns (roughly two trade sizes lower ampacity).
- Adjustment for continuous loads — sizing at 125% happens before this table.